AP 33

Product: PERKINS Alternator: ECP 28-VL/4 C Control System: DSE 6120
INTRODUCTION
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
Certificate
  TS ISO 8528
  TS ISO 9001-2008
  CE
  SZUTEST
  2000/14/EC
General Characteristics
Model Name AP 33
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model PERKINS - 1103A-33G
Alternator Made and Model Mecc Alte - ECP 28-VL/4 C
Control Panel Model DSE 6120
Canopy AK 21
3 Phase, 50 Hz, PF 0.8
Voltage STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 33 26.4 30 24.0 47.63
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine PERKINS
Engine Model 1103A-33G
NO. OF CYLINDERS AND BUILD 3 cylinders - in line
BORE AND STROKE mm 105 X 127
TOTAL DISPLACEMENT L 3.3
Aspiration Naturally Aspirated
COMPRESSION RATIO 19.25:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 8.3
Standby Power (kW/HP) 31/41,55
Prime Power 28.2/37,80
Block Heater QTY
1
Block Heater Power (Watt) 500
Fuel Type
Diesel
Injection Type and System
Direct
Type of Fuel Pump
Delphi Rotary Type
Governor System
Mechanic
Operating Voltage (Vdc)
12 Vdc
Battery and Capacity (Qty/Ah) 1x55
Charge Alternator (A)
65
Cooling Method
Water Cooled
Coolant Capacity (engine only / with radiator) (lt) /10.2
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (lt/hr) 7.1
Fuel Cons. Prime With %75 Load (lt/hr) 5.4
Fuel Cons. Prime With %50 Load (lt/hr) 3.9
ALTERNATOR SPECIFICATIONS
Manufacturer Mecc Alte
Alternator Made and Model ECP 28-VL/4 C
Frequency (Hz) Hz 50
Power (kVA) kVA 30
Design   4 Pole,  Brushless
Voltage V 400
Phase 3
A.V.R. DSR
Voltage Regulation (+/-) 1
Insulation System H
Protection IP23
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 141.8
COOLING AIR (m³/min) m3 6.6
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
665 1691 970 1221 80
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
AK 21
880 2102 1026 1290 80
STANDARD SPECIFICATIONS
Water cooled, Diesel engine 
Radiator with mechanical fan 
Protective grille for rotating and hot parts 
Electric starter and charge alternator 
Starting battery (with lead acid) including rack and cables 
Engine coolant heater 
Base frame design incorporates an integral fuel tank and anti-vibration isolators 
Flexible fuel connection hoses 
Single bearing, class H alternator 
Industrial exhaust silencer and steel bellows supplied separately(for open sets) 
Static battery charger 
Manual for application and installation
OPTIONAL EQUIPMENTS
ENGINE
• Fuel-Water Seperator Filter
• Low water level alarm
• Oil heater
ALTERNATOR
• Anti-Condensation Heater
• Over sized alternator
• Main line circuit breaker
CONTROL SYSTEM
• Remote annunciator panel
• Remote relay output
• Alarm output relays
• Remote communication with modem
• Earth fault, single set
• Charge Ammeter
TRANSFER SWITCH
• Three or four pole contactor
• Three or four pole motor operated circuit breaker
OTHER ACCESSORIES
• Main Fuel Tank
• Automatic or manual fuel filling system
• Manual oil drain pump
• Residential silencer
• Enclosure: weater protective or sound attenuated
• Duct adapter ( on radiator)
• Inlet and outlet motorised louvers
• Inlet and outlet acoustic baffles
• Trailer
• Tool kit for maintenance
• Supplied with oil and coolant - 30 °C
• Battery isolating switch
Control System: DSE 6120
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Devices
●DSE, model 6120 Auto Mains Failure control module.
●Battery charger input 198-264 volt, output 27,6 V 5 A (24 V) or 13,8 Volt 5A (12V)
●Emergency stop push button and fuses for control circuits.
CONSTRUCTION and FINISH
●Components installed in sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion resistant surface. Polyester composite powder topcoat forms high gloss and extremely durable finish. Lockable and hinged panel door provides easy access to components.
INSTALLATION
Control panel is mounted on baseframe with steel stand. Located at the right side of the generator set (When you look at the Gen.Set. from Alternator)
GENERATING SET CONTROL UNIT
The DSE 6120 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant temperature running hours and battery volts.
Module monitors the mains supply and switch over to the generator when the mains power fails.
The DSE6120 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving true first up fault condition of Gen. Set failure.The LCD display indicates the fault.

STANDARD SPECIFICATIONS
●Microprocessor controlled.
●LCD display makes information easy to read.
●Automatically transfers between mains (utilty) and generator power.
●Manual programming on front panel.
●User-friendly set-up and button layout.
●Remote start.
●Event logging (50) showing date and time.
●Controls: Stop/Reset, Manual, Auto, Test, Start, buttons. An additional push button next to the LCD display is used to scroll through the modules' metering displays.

Instruments
ENGINE
●Engine speed.
●Oil pressure.
●Coolant temperature.
●Run time.
●Battery volts.
●Configurable timing.

GENERATOR
●Voltage (L-L, L-N).
●Current (L1-L2-L3).
●Frequency.
●Gen. Set ready.
●Gen. Set enabled.

MAINS
●Mains ready.
●Mains enabled.
Protection Circuits
WARNING 
●Charge failure. 
●Battery Low/High voltage. 
●Fail to stop. 
●Low /High generator voltage. 
●Under /Over generator frequency. 
●Over /Under speed. 
●Low oil pressure. 
●High coolant temperature. 

SHUT DOWNS 
●Fail to start.
●Emergency stop. 
●Low oil pressure. 
●High coolant temperature. 
●Over /Under speed. 
●Under/over generator frequency. 
●Under/over generator voltage. 
●Oil pressure sensor open. 
●Coolant temperature sensor open. 

ELECTRICAL TRIP 
●Generator over current.


Options
●Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)
●Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).
Standards
●Elecrical Safety / EMC compatibility
●BS EN 60950 Electrical business equipment.
●BS EN 61000-6-2 EMC immunity standard.
●BS EN 61000-6-4 EMC emission standard
STATIC BATTERY CHARGER
● Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency.
● Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volt and 27,6 V for 24 V . Input 198 - 264 volt AC.
● The charger is fitted with a protection diode across the output.
● Connect charge fail relay coil between positive output and CF output.
● They are equipped with RFI filter to reduce electrical noise radiated from the device.
● Galvanically isolated input and output typically 4kV for high reliability.
Canopy: AK 21
1. Steel structures 
2. Emergency stop push button 
3. Control panel is right side of the set. 
4. Corrosion.resistant locks and hinges 
5. Base frame .fuel tank. 
6. Lockable, large doors on each side. 
7. Lifting Points
INTRODUCTION
Sound–attenuated and Weather-protective Enclosures Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
STANDARD SPECIFICATIONS
Compact footprint, low profile design. 
Enclosure, generator set, exhaust system and fuel tank are pre-ssembled, pre-integrated and shipped as one package 
Body made from steel components treated with polyester powder coating 
Fire retardant foam insulation 
Easy access to all service points 
Exhaust system inside canopy 
Large doors on each side 
Control panel viewing window in a lockable access door 
Emergency stop push button mounted on enclosure exterior 
Cooling fan and battery charging alternator fully guarded 
Fuel fill and battery can only be reached via lockable access doors. 
Lifting points on the top of canopy and base frame 
Customer options available to meet your applications needs. 
Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been aproved by the notified body Szutest

CANOPY MODEL AK 21
WIDTH mm. 1026
LENGTH mm. 2102
HEIGHT mm. 1290
TANK CAPACITY (lt.) Lt. 80