ALG 45

Product: LOVOL NG Alternator: ECP 32-3S/4 B Control System: DSE 6120
INTRODUCTION
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
Certificate
  TS ISO 8528
  CE
  SZUTEST
  2000/14/EC
General Characteristics
Model Name ALG 45
Frequency (Hz) 50
Fuel Type Natural Gas
Engine Made and Model LOVOL NG - 1006NG
Alternator Made and Model Mecc Alte - ECP 32-3S/4 B
Control Panel Model DSE 6120
Canopy AK40-ALG45
3 Phase, 50 Hz, PF 0.8
Voltage STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 45 36.0 41 32.8 64.95
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine LOVOL NG
Engine Model 1006NG
NO. OF CYLINDERS AND BUILD 6 cylinders - in line
BORE AND STROKE mm 100 X 127
TOTAL DISPLACEMENT L 5.98
Aspiration Naturally Aspirated
COMPRESSION RATIO 10.0:3
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 16.1
Standby Power (kW/HP) 40/44
Block Heater QTY
1
Block Heater Power (Watt) 1000
Fuel Type
Natural Gas
Operating Voltage (Vdc)
12 Vdc
Battery and Capacity (Qty/Ah) 1x56
Cooling Method
Water Cooled
Coolant Capacity (engine only / with radiator) (lt) /23.1
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (m3/hr) 7,8
ALTERNATOR SPECIFICATIONS
Manufacturer Mecc Alte
Alternator Made and Model ECP 32-3S/4 B
Frequency (Hz) Hz 50
Power (kVA) kVA 42.5
Voltage V 400
Phase 3
A.V.R. DSR
Voltage Regulation (+/-) 1
Insulation System H
Protection IP23
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 209
COOLING AIR (m³/min) m3 11.8
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
2150 1050 1321
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
AK40-ALG45
1270 3100 1050 1641 N/A
STANDARD SPECIFICATIONS
Heavy duty, water cooled naturalgas engine 
46/50 °C ambient rated radiator with mechanical fan 
Protective grille for fan and rotating parts 
Electric starter and charge alternator 
Starting battery (with lead acid) including rack and cables 
Engine jacket cooling heater 
Base frame design incorporates an integral fuel tank and anti-vibration isolators 
Flexible fuel connection hoses 
Single bearing, class H alternator 
Industrial exhaust silencer and steel belows supplied separately 
Static battery charger 
Manual for use and installation
OPTIONAL EQUIPMENTS
ENGINE
• Remote Radiator Cooling
• Low Coolant level alarm
ALTERNATOR
• Anti-Condensation heater
• Over sized alternator
• Main line circuit breaker
CONTROL SYSTEM
• Remote annunciator panel
• Uzağa alarm paneli
• Alarm output relays
• Earth fault, single set
• Charging ammeter
TRANSFER SWITCH
• Üç kutuplu kontaktör
• Four Pole Contactor
VISE ACCESSORIES
• Manual oil drain pump
• Electrical oil drain pump
• Enclosure: weater protective or sound attenuated
• Duct adapter ( on radiator)
• Inlet and outlet motorised louvers
• Tool kit for maintenance
Control System: DSE 6120
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Devices
●DSE, model 6120 Auto Mains Failure control module.
●Battery charger input 198-264 volt, output 27,6 V 5 A (24 V) or 13,8 Volt 5A (12V)
●Emergency stop push button and fuses for control circuits.
CONSTRUCTION and FINISH
●Components installed in sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion resistant surface. Polyester composite powder topcoat forms high gloss and extremely durable finish. Lockable and hinged panel door provides easy access to components.
INSTALLATION
Control panel is mounted on baseframe with steel stand. Located at the right side of the generator set (When you look at the Gen.Set. from Alternator)
GENERATING SET CONTROL UNIT
The DSE 6120 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant temperature running hours and battery volts.
Module monitors the mains supply and switch over to the generator when the mains power fails.
The DSE6120 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving true first up fault condition of Gen. Set failure.The LCD display indicates the fault.

STANDARD SPECIFICATIONS
●Microprocessor controlled.
●LCD display makes information easy to read.
●Automatically transfers between mains (utilty) and generator power.
●Manual programming on front panel.
●User-friendly set-up and button layout.
●Remote start.
●Event logging (50) showing date and time.
●Controls: Stop/Reset, Manual, Auto, Test, Start, buttons. An additional push button next to the LCD display is used to scroll through the modules' metering displays.

Instruments
ENGINE
●Engine speed.
●Oil pressure.
●Coolant temperature.
●Run time.
●Battery volts.
●Configurable timing.

GENERATOR
●Voltage (L-L, L-N).
●Current (L1-L2-L3).
●Frequency.
●Gen. Set ready.
●Gen. Set enabled.

MAINS
●Mains ready.
●Mains enabled.
Protection Circuits
WARNING 
●Charge failure. 
●Battery Low/High voltage. 
●Fail to stop. 
●Low /High generator voltage. 
●Under /Over generator frequency. 
●Over /Under speed. 
●Low oil pressure. 
●High coolant temperature. 

SHUT DOWNS 
●Fail to start.
●Emergency stop. 
●Low oil pressure. 
●High coolant temperature. 
●Over /Under speed. 
●Under/over generator frequency. 
●Under/over generator voltage. 
●Oil pressure sensor open. 
●Coolant temperature sensor open. 

ELECTRICAL TRIP 
●Generator over current.


Options
●Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)
●Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).
Standards
●Elecrical Safety / EMC compatibility
●BS EN 60950 Electrical business equipment.
●BS EN 61000-6-2 EMC immunity standard.
●BS EN 61000-6-4 EMC emission standard
STATIC BATTERY CHARGER
● Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency.
● Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volt and 27,6 V for 24 V . Input 198 - 264 volt AC.
● The charger is fitted with a protection diode across the output.
● Connect charge fail relay coil between positive output and CF output.
● They are equipped with RFI filter to reduce electrical noise radiated from the device.
● Galvanically isolated input and output typically 4kV for high reliability.
Canopy: AK40-ALG45
STANDARD SPECIFICATIONS


CANOPY MODEL AK40-ALG45
WIDTH mm. 1050
LENGTH mm. 3100
HEIGHT mm. 1641
TANK CAPACITY (lt.) Lt. N/A