ADG 415

Product: HYUNDAI Alternator: ECO 40-1S/4 B Control System: DSE 7320
INTRODUCTION
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
Certificate
  TS ISO 8528
  CE
  SZUTEST
  2000/14/EC
General Characteristics
Model Name ADG 415
Frequency (Hz) 50
Fuel Type Natural Gas
Engine Made and Model HYUNDAI - GV222TI
Alternator Made and Model Mecc Alte - ECO 40-1S/4 B
Control Panel Model DSE 7320
Canopy MS 86 GZ
3 Phase, 50 Hz, PF 0.8
Voltage STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 415 332.00 375 300.00 599.02
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine HYUNDAI
Engine Model GV222TI
NO. OF CYLINDERS AND BUILD 12 cylinders - V type
BORE AND STROKE mm 128 X 142
TOTAL DISPLACEMENT L 21.927
Aspiration Turbo Charged and Intercooled(Water to Air)
COMPRESSION RATIO 10.5:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 40
Standby Power (kW/HP) 385/523
Prime Power 350/476
Block Heater QTY
1
Block Heater Power (Watt) 3000
Fuel Type
Natural Gas
Operating Voltage (Vdc)
24 Vdc
Battery and Capacity (Qty/Ah) 2x143
Charge Alternator (A)
45
Cooling Method
Water Cooled
Cooling Fan Air Flow (m3/min) 670
Coolant Capacity (engine only / with radiator) (lt) 44/285.3
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (m3/hr) 95.2
Fuel Cons. Prime With %75 Load (m3/hr) 88.2
Fuel Cons. Prime With %50 Load (m3/hr) 73.4
ALTERNATOR SPECIFICATIONS
Manufacturer Mecc Alte
Alternator Made and Model ECO 40-1S/4 B
Frequency (Hz) Hz 50
Power (kVA) kVA 400
Design   4 Pole,  Brushless
Voltage V 400
Phase 3
A.V.R. DER1
Voltage Regulation (+/-) 0.5
Insulation System H
Protection IP23
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 1049
COOLING AIR (m³/min) m3 54
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
4730 3580 1800 2040
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
MS 86 GZ
5670 5410 1860 2650 N/A
STANDARD SPECIFICATIONS
-
OPTIONAL EQUIPMENTS
ENGINE
• Low Coolant level alarm
• Oil heater

ALTERNATOR
• Anti-Condensation heater
• Over sized alternator
• Single Phase ( 4 lead)
• Main line circuit breaker

CONTROL SYSTEM
• Automatic synchronising and power control system ( multi gen-set Parallel )
• Paralel system with mains.
• Remote annunciator panel
• Uzağa alarm paneli
• Alarm output relays
• Remote communication with modem
• Earth fault, single set
• Charging ammeter

TRANSFER SWITCH
• Four Pole Contactor

VISE ACCESSORIES
• Manual oil drain pump
• Electrical oil drain pump
• Enclosure: weater protective or sound attenuated
• Duct adapter ( on radiator)
• Inlet and outlet motorised louvers
• Tool kit for maintenance
• 1500/3000 hours maintenance kit
• Supplied with oil and coolant - 30 °C
• Automatic transfer switch
Control System: DSE 7320
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Devices
DSE, model 7320 Auto Mains Failure control module Static battery charger Emergency stop push button and fuses for control circuits
CONSTRUCTION and FINISH
Comonents installed in sheet steel enclosure.
Phosphate chemical, pre-coating of steel provides corrosion resistant surface
Polyester composite powder topcoat forms high gloss and extremely durable finish
Lockable hinged panel door provides for easy component access
INSTALLATION
Control panel is mounted generating set baseframe on robust steel stand or power module. Located at side of generating set with properly panel visibility.
GENERATING SET CONTROL UNIT
The DSE 7320 conrol module is a standard addition to our generator sets from 220 kVA upwards and it has been designed to start and stop diesel andgas generating sets that include electronic and non electronic engines.
The DSE 7320 includes the additional capability of being able to monitor a mains (utility) supply and is therefore suitable for controlling a standby generating set in conjunction with an automatic transfer switch.
The DSE7320 also indicates operational status and fault conditions, automatically shutting down the generating set and indicating faults by means of its LCD display on the front panel.

STANDARD SPECIFICATIONS
Microprocessor controlled
- 132 x 64 pixel LCD display makes information easy to read
- Front panel programming and also via PC software
- Soft touch membrane keypad and five key menu navigation
- Remote communications via RS232, RS485 and ethernet.
- Event logging (50) showing date and time
- Multiple date and time engine exercise mode and maintenance scheduler
- Engine block heater control.
- Controls; stop, manuel, auto, test, start, mute lamb test/transfer to generator, transfer to mains, menu navigation.

Instruments
ENGINE
Engine speed
Oil pressure
Coolant temperature
Run time Battery volts
Engine maintenance due

GENERATOR
Voltage (L-L, L-N)
Current (L1-L2-L3)
Frequency
Earth current
kW
Pf
kVAr
kWh, kVAh, kVArh
Phase sequence

MAINS
Voltage (L-L, L-N)
Frequency
Protection Circuits
WARNING
Charge failure
Battery under voltage
Fail to stop
Low fuel level (opt.)
kW over load
Negative phase sequence
Loss of speed signal

PRE-ALARMS
Low oil pressure
High engine temperature
Low engine temperature
Over /Under speed
Under/over generator frequency
Under/over generator voltage
ECU warning

SHUT DOWNS
Fail to start
Emergency stop
Low oil pressure
High engine temperature
Low coolant level
Over /Under speed
Under/over generator frequency
Under/over generator voltage
Oil pressure sensor open
Phase rotation

ELECTRICAL TRIP
Earth fault
kW over load
Generator over current
Negative phase sequence


Options
High oil temperature shut down
Low fuel level shut down
Low fuel level alarm
High fuel level alarm

EXPANSION MODULES
Editional LED module (2548)
Expension relay module (2157)
Expansion input module (2130)
Standards
Elecrical Safety / EMC compatibility

BS EN 60950 Electrical business equipment
BS EN 61000-6-2 EMC immunity standard
BS EN 61000-6-4 EMC emission standard
STATIC BATTERY CHARGER
Battery charger is manufactured with switching-mode and SMD technology and it has high efficincy.
Battery charger models' output V-I characteristic is very close to square
2405 has fully output shot circuit protection and ıt can be used as a current source.
2405 charger has high efficiency, long life, low failure rate, light weight and low heat radiated in accordance with linear alternatives.
The charger is fitted with a protection diode across the output.
Charge fail output is available.
Connect charge fail relay coil between positive output and CF output.
Input: 196-264V.
Output: 27,6V 5A or 13,8V 5A.
Canopy: MS 86 GZ
STANDARD SPECIFICATIONS


CANOPY MODEL MS 86 GZ
WIDTH mm. 1860
LENGTH mm. 5410
HEIGHT mm. 2650
TANK CAPACITY (lt.) Lt. N/A