AC 500

Product: CUMMINS Alternator: ECO 40-3S/4 B Control System: DSE 7320
INTRODUCTION
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
Certificate
  TS ISO 8528
  CE
  SZUTEST
  2000/14/EC
General Characteristics
Model Name AC 500
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model CUMMINS - QSX15-G6
Alternator Made and Model Mecc Alte - ECO 40-3S/4 B
Control Panel Model DSE 7320
Canopy MS 80
3 Phase, 50 Hz, PF 0.8
Voltage STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper
kVA kW kVA kW
400/231 500 400.0 455 364.0 721.71
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.

PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine CUMMINS
Engine Model QSX15-G6
NO. OF CYLINDERS AND BUILD 6 cylinders - in line
BORE AND STROKE mm 137 X 169
TOTAL DISPLACEMENT L 14.9
Aspiration Turbo Charged and Charge Air Cooled
COMPRESSION RATIO 17.2:1
RATED SPEED (RPM) d/dk 1500
OIL CAPACITY L 90.8
Standby Power (kW/HP) 459/615
Prime Power 414/555
Block Heater QTY
1
Block Heater Power (Watt) 3000
Fuel Type
Diesel
Injection Type and System
XPI
Type of Fuel Pump
HPCR (High Pressure Common Rail)
Governor System
ECM
Operating Voltage (Vdc)
24 Vdc
Battery and Capacity (Qty/Ah) 2x120
Cooling Method
Water Cooled
Coolant Capacity (engine only / with radiator) (lt) 33/
Air Filter
Dry Type
Fuel Cons. Prime With %100 Load (lt/hr) 95
Fuel Cons. Prime With %75 Load (lt/hr) 75
Fuel Cons. Prime With %50 Load (lt/hr) 53
ALTERNATOR SPECIFICATIONS
Manufacturer Mecc Alte
Alternator Made and Model ECO 40-3S/4 B
Frequency (Hz) Hz 50
Power (kVA) kVA 500
Design   4 Pole,  Brushless
Voltage V 400
Phase 3
A.V.R. DER1
Voltage Regulation (+/-) 0.5
Insulation System H
Protection IP23
Rated Power Factor 0.8
WEIGHT COMP. GENERATOR (Kg) 1208
COOLING AIR (m³/min) m3 54
SIZE and WEIGHT
Open Type DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
3815 3205 1550 2103 850
CANOPY DRY WEIGHT (kg.)
(kg.)
LENGTH
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
MS 80
4815 4807 1606 2485 850
STANDARD SPECIFICATIONS
Water cooled, Diesel engine 
Radiator with mechanical fan 
Protective grille for rotating and hot parts 
Electric starter and charge alternator 
Starting battery (with lead acid) including rack and cables 
Engine coolant heater 
Base frame design incorporates an integral fuel tank and anti-vibration isolators 
Flexible fuel connection hoses 
Single bearing, class H alternator 
Industrial exhaust silencer and steel bellows supplied separately(for open sets) 
Static battery charger 
Manual for application and installation 
Generators Sets’ voltage and frequency regulation comply with ISO 8528-5 
Generators Sets’ can take 100% load at one step according to NFPA110
OPTIONAL EQUIPMENTS
ENGINE
• Fuel-Water Seperator Filter
• Oil heater

ALTERNATOR
• Anti-Condensation Heater
• Over sized alternator
• Main line circuit breaker

CONTROL SYSTEM
• Automatic synchronising and power control system ( multi gen-set Parallel )
• Remote annunciator panel
• Alarm output relays
• Remote communication with modem
• Earth fault, single set
• Charge Ammeter

TRANSFER SWITCH
• Three or four pole contactor
• Three or four pole motor operated circuit breaker

OTHER ACCESSORIES
• Main Fuel Tank
• Automatic or manual fuel filling system
• Electrical oil drain pump
• Low and high fuel level alarm
• Residential silencer
• Enclosure: weater protective or sound attenuated
• Duct adapter ( on radiator)
• Inlet and outlet motorised louvers
• Inlet and outlet acoustic baffles
• Trailer
• Tool kit for maintenance
• 1500/3000 hours maintenance kit
• Double wall chassis
• Supplied with oil and coolant - 30 °C
• Battery isolating switch
Control System: DSE 7320
1. Menu navigation buttons 
2. Close mains button 
3. Main Status and instrumentation display 
4. Alarm LED's 
5. Close generator button 
6. Status LED's 
7. Operation selecting buttons
Devices
DSE, model 7320 Auto Mains Failure control module Static battery charger Emergency stop push button and fuses for control circuits
CONSTRUCTION and FINISH
Comonents installed in sheet steel enclosure.
Phosphate chemical, pre-coating of steel provides corrosion resistant surface
Polyester composite powder topcoat forms high gloss and extremely durable finish
Lockable hinged panel door provides for easy component access
INSTALLATION
Control panel is mounted generating set baseframe on robust steel stand or power module. Located at side of generating set with properly panel visibility.
GENERATING SET CONTROL UNIT
The DSE 7320 conrol module is a standard addition to our generator sets from 220 kVA upwards and it has been designed to start and stop diesel andgas generating sets that include electronic and non electronic engines.
The DSE 7320 includes the additional capability of being able to monitor a mains (utility) supply and is therefore suitable for controlling a standby generating set in conjunction with an automatic transfer switch.
The DSE7320 also indicates operational status and fault conditions, automatically shutting down the generating set and indicating faults by means of its LCD display on the front panel.

STANDARD SPECIFICATIONS
Microprocessor controlled
- 132 x 64 pixel LCD display makes information easy to read
- Front panel programming and also via PC software
- Soft touch membrane keypad and five key menu navigation
- Remote communications via RS232, RS485 and ethernet.
- Event logging (50) showing date and time
- Multiple date and time engine exercise mode and maintenance scheduler
- Engine block heater control.
- Controls; stop, manuel, auto, test, start, mute lamb test/transfer to generator, transfer to mains, menu navigation.

Instruments
ENGINE
Engine speed
Oil pressure
Coolant temperature
Run time Battery volts
Engine maintenance due

GENERATOR
Voltage (L-L, L-N)
Current (L1-L2-L3)
Frequency
Earth current
kW
Pf
kVAr
kWh, kVAh, kVArh
Phase sequence

MAINS
Voltage (L-L, L-N)
Frequency
Protection Circuits
WARNING
Charge failure
Battery under voltage
Fail to stop
Low fuel level (opt.)
kW over load
Negative phase sequence
Loss of speed signal

PRE-ALARMS
Low oil pressure
High engine temperature
Low engine temperature
Over /Under speed
Under/over generator frequency
Under/over generator voltage
ECU warning

SHUT DOWNS
Fail to start
Emergency stop
Low oil pressure
High engine temperature
Low coolant level
Over /Under speed
Under/over generator frequency
Under/over generator voltage
Oil pressure sensor open
Phase rotation

ELECTRICAL TRIP
Earth fault
kW over load
Generator over current
Negative phase sequence


Options
High oil temperature shut down
Low fuel level shut down
Low fuel level alarm
High fuel level alarm

EXPANSION MODULES
Editional LED module (2548)
Expension relay module (2157)
Expansion input module (2130)
Standards
Elecrical Safety / EMC compatibility

BS EN 60950 Electrical business equipment
BS EN 61000-6-2 EMC immunity standard
BS EN 61000-6-4 EMC emission standard
STATIC BATTERY CHARGER
Battery charger is manufactured with switching-mode and SMD technology and it has high efficincy.
Battery charger models' output V-I characteristic is very close to square
2405 has fully output shot circuit protection and ıt can be used as a current source.
2405 charger has high efficiency, long life, low failure rate, light weight and low heat radiated in accordance with linear alternatives.
The charger is fitted with a protection diode across the output.
Charge fail output is available.
Connect charge fail relay coil between positive output and CF output.
Input: 196-264V.
Output: 27,6V 5A or 13,8V 5A.
Canopy: MS 80
1. Steel structures. 
2. Emergency stop push button. 
3. Control panel is mounted on the baseframe . Located at the right side of the generator set. 
4. Corrosion-resistant locks and hinges. 
5. Oil could be drained via valve and a hose 
6. Exhaust system in the canopy. 
7. Special large access doors for easy maintanance 
8. In front and back side special large access doors for easy maintanance 
9. Base frame -fuel tank. 
10. Lifting points similar to ISO container , located on each top corner of the canopy. 
11. The cap on the canopy provides easy accsess to radiator cap. 
12. Sound proofing materials 
13. Plastic air intake pockets.
INTRODUCTION
Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
STANDARD SPECIFICATIONS
Compact footprint, low profile design. 
Enclosure, generator set, exhaust system and fuel tank are pre-ssembled, pre-integrated and shipped as one package 
Body made from steel components treated with polyester powder coating 
Fire retardant foam insulation 
Easy access to all service points 
Exhaust system inside canopy 
Large doors on each side 
Control panel viewing window in a lockable access door 
Emergency stop push button mounted on enclosure exterior 
Cooling fan and battery charging alternator fully guarded 
Fuel fill and battery can only be reached via lockable access doors. 
Lifting points on the top of canopy and base frame 
Customer options available to meet your applications needs. 
Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been aproved by the notified body Szutest

CANOPY MODEL MS 80
WIDTH mm. 1606
LENGTH mm. 4807
HEIGHT mm. 2485
TANK CAPACITY (lt.) Lt. 850